Duct Size Calculator

Turn airflow into round diameter or rectangular width × height from a target velocity or friction rate.

Free · No sign-up · Runs in your browser

How to use the duct size calculator

Ducts that are too small whistle and starve rooms; ducts that are oversized waste space and can drop velocity so low that dirt settles. This calculator gives ACCA Manual D–style starting sizes from airflow and either a target velocity or a friction rate, then shows both round diameter and a rectangular equivalent at your aspect ratio. Treat the results as layout estimates before a full Manual D run.

  1. Choose units — cfm / inches / fpm, or L/s / mm / m/s.
  2. Enter the design airflow for that trunk or branch (from Manual J / room loads, not just tons × 400).
  3. Pick velocity or friction mode. Velocity mode uses role defaults (trunk / branch / return) unless you choose custom. Friction mode targets a residential equal-friction rate such as 0.08–0.10 in.wg per 100 ft.
  4. Set rectangular aspect ratio if the duct must fit a shallow bay, then read round OD and width × height.

Duct sizing formulas

Area (ft²) = cfm ÷ velocity (fpm)
Round diameter (in) = 12 × √(4 × Area / π) ≈ 13.54 × √(cfm / velocity)
Rectangular: choose aspect r = W/H, then H = √(Area_free / r), W = r × H (inside clear dimensions)
Equivalent round rule of thumb: D_eq ≈ 1.30 × (W × H)^0.625 / (W + H)^0.25
Friction estimate (Darcy-style approximation for smooth metal): ΔP/100 ft scales roughly with velocity² / D5 — chart values used here are calibrated estimates

Default velocities: supply trunk 800 fpm (4.1 m/s), supply branch 650 fpm (3.3 m/s), return 600 fpm (3.0 m/s). Friction defaults to 0.10 in.wg/100 ft (0.82 Pa/m). Rectangular sizes keep a practical inside dimension rounded to common 1 in / 25 mm increments.

RoleTypical velocityMetric
Supply trunk700–900 fpm3.6–4.6 m/s
Supply branch600–700 fpm3.0–3.6 m/s
Return500–700 fpm2.5–3.6 m/s
Flex ductOften ≤ 600 fpm≤ 3.0 m/s

Worked examples

A 400 cfm supply trunk

At 800 fpm, area = 400 ÷ 800 = 0.5 ft². Round diameter ≈ 1.128 × √(400/800) = 9.6 in, so use a 10 in round trunk. At 2:1 aspect, a rectangular equivalent near 14 × 7 in keeps similar area after allowing for aspect penalty. Friction at 0.10 in/100 ft lands in a similar 9–10 in round band on a ductulator.

A 120 cfm bedroom branch

At 650 fpm branch velocity, diameter ≈ 1.128 × √(120/650) ≈ 5.5 in → a 6 in round run or a 10 × 4 in rectangular boot feed. That is a common residential bedroom size when the Manual J load is around 3,000 BTU/h.

Metric living-room run

190 L/s (≈ 400 cfm) on a supply trunk at 4.1 m/s needs about 240 mm round duct. A 2:1 rectangular chase might land near 350 × 175 mm inside. Check noise if you push much past 5 m/s in occupied rooms.

Who this calculator helps

  • Architects reserving shaft and joist space before HVAC drawings arrive.
  • HVAC designers and technicians sketching equal-friction starting sizes.
  • Energy auditors and renovators checking whether existing trunks can carry a heat-pump airflow.
  • Self-builders coordinating duct chases with framing and lighting.

Practical tips

  • Derive room CFM from loads with the BTU calculator and the heat loss calculator, and fresh-air CFM with the ventilation calculator.
  • Keep rectangular aspect ratios under 4:1; wide flat ducts need a larger equivalent area for the same friction.
  • Flex duct needs larger diameters than hard pipe for the same CFM — size from the flex manufacturer's friction chart.
  • Seal and insulate ducts in unconditioned spaces; leakage shows up as rooms that never hit setpoint.
  • Leave static-pressure margin for the filter, coil and long fitting strings — duct friction is only part of ESP.

Coordinating grille locations with furniture? Test the layout on a photo with Room Redesign.

From numbers to pictures

See the space before it's built.

Once the plan works on paper, BasedFrame turns a sketch, a massing model or a site photo into a photoreal render in seconds. Try Sketch to Render or Room Redesign with free credits.

Try BasedFrame free

FAQ

Duct Size Calculator FAQ

How do I calculate duct size from CFM?

Pick a target velocity or friction rate, then solve for cross-section. For round duct, diameter D (inches) ≈ 1.128 × √(cfm ÷ velocity_fpm) when velocity is in feet per minute. Designers often start near 700–900 fpm for supply trunks, 600–700 fpm for branches, and about 0.08–0.10 in.wg per 100 ft of friction for residential equal-friction sizing.

What is the equal-friction method?

You choose a friction rate (commonly 0.08 or 0.10 in.wg per 100 ft for homes) and size every duct segment so that CFM and that friction land on the same duct calculator or ductulator chart. It keeps pressure drops predictable before you add fittings. This tool approximates that chart; a full ACCA Manual D run still needs fitting equivalent lengths and equipment ESP.

Round vs rectangular duct — which is better?

Round duct is more efficient for the same friction and usually quieter and cheaper to seal. Rectangular duct fits shallow joist bays and chase walls. When you convert, use an equivalent round diameter and then pick width × height at your aspect ratio; keep aspect ratios under about 4:1 so friction does not climb too far.

What velocity should I use for supply and return?

Rules of thumb: main supply trunks ~700–900 fpm, supply branches ~600–700 fpm, returns ~500–700 fpm, and flexible duct often lower. Higher velocity shrinks the duct but raises noise and friction. Living spaces usually stay toward the quieter end of the range.

How do I convert CFM to L/s?

1 cfm ≈ 0.4719 L/s, and 1 L/s ≈ 2.119 cfm. Metric designers also talk in m³/h (1 L/s = 3.6 m³/h). The calculator switches labels and defaults when you pick metric units.

What friction rate is typical in a house?

Many residential Manual D designs start at 0.08 or 0.10 in.wg per 100 ft for metal duct. Restrictive filters, long flex runs and many elbows eat external static pressure, so leaving margin on friction helps the blower hit the design CFM.

Can I size ducts from tonnage alone?

A crude check is about 400 cfm per ton of cooling, but room-by-room Manual J loads should drive the CFM before you size ducts. Use the BTU / heat-loss tools for load, then this calculator for duct geometry.

Is this a full ACCA Manual D calculation?

No. It is Manual D–style guidance for early layout: round diameter, rectangular equivalents, velocity and a friction estimate. Final designs need fitting losses, available static pressure, and code or manufacturer limits.