Lighting Calculator

Pick a room type or set your own lux level, enter the room size and fitting output, and get total lumens, the number of fittings, installed watts and a suggested grid.

Free · No sign-up · Runs in your browser

How to use the lighting calculator

Getting the amount of light right is one of the first lighting design decisions on any interior. Too little and a kitchen or office feels gloomy and fails the brief; too much and you waste energy, blow the lighting power budget and create glare. This calculator uses the lumen method, the standard hand calculation for general lighting, to turn a target light level into a number of fittings.

  1. Choose a room type to load a typical target illuminance, or choose Custom and type your own. Switch units to work in feet and footcandles.
  2. Enter the room length and width and the rated output of one fitting in lumens, taken from the manufacturer's data sheet (use the fitting output, not the bare LED chip).
  3. Adjust the factors if you know them. The defaults (utilisation 0.6, maintenance 0.8) suit a pale room with LED downlights or panels.
  4. Read the results: total lumens needed, number of fittings, the light level you'll actually get with that number, installed watts, power density and a suggested grid with spacings.

Lumen method formulas

Lumens needed = E × A ÷ (UF × MF)
Fittings N = Lumens needed ÷ lumens per fitting (round up)
Achieved E = N × lumens per fitting × UF × MF ÷ A
Installed watts = N × lumens per fitting ÷ efficacy
1 footcandle = 1 lm/ft² = 10.764 lux

E is the target illuminance on the working plane (lux or footcandles), A the floor area (m² or ft²), UF the utilisation factor and MF the maintenance factor. Because a lux is a lumen per square metre and a footcandle a lumen per square foot, the formula works in either system as long as you keep area and light level in matching units.

SpaceTypical luxFootcandles
Bedroom, hallway, stairs10010
Living room15015
Dining room, bathroom20020
Kitchen (general), classroom30030
Kitchen worktop, office desk, retail50050
Drawing board, detailed work75075

These are typical design values drawn from EN 12464-1, the SLL Code for Lighting and IES recommendations. Always check the standard or client brief that applies to your project.

Worked examples

A living room

A 5 × 4 m living room (20 m²) at 150 lux, with UF 0.6 and MF 0.8, needs 150 × 20 ÷ 0.48 = 6,250 lumens. With 800-lumen downlights that's 7.8, so 8 fittings. At 90 lm/W they draw about 71 W, or 3.6 W/m². In practice you'd put some of those lumens into lamps and wall lights on dimmers.

A kitchen in footcandles

A 12 × 10 ft kitchen (120 ft²) needs 30 footcandles of general light. Lumens = 30 × 120 ÷ 0.48 = 7,500. Using 1,000-lumen recessed lights gives 7.5, so 8 fittings. For even spacing the calculator suggests a 3 × 3 grid of 9 lights at about 4 × 3.3 ft centres, giving about 36 fc. Under-cabinet strips then lift the worktops toward 50 fc.

An open-plan studio

A 10 × 8 m architecture studio (80 m²) at 500 lux needs 500 × 80 ÷ 0.48 ≈ 83,300 lumens. With 4,000-lumen LED panels that's 20.8, so 21 panels. The calculator suggests a 6 × 4 grid (24 panels, roughly 1.7 × 2 m centres), which gives about 576 lux and a tidy, even ceiling.

Who this calculator helps

  • Architects fixing ceiling layouts, coordinating fittings with grids and services, and checking lighting power density at concept stage.
  • Interior designers working out how many downlights, pendants or tracks a scheme really needs.
  • Lighting and electrical designers doing a quick lumen-method check before modelling in DIALux or AGi32.
  • Electricians and contractors pricing jobs and checking that a drawing has enough fittings.
  • Homeowners choosing LED bulbs and deciding how many recessed lights to put in a room.

Practical tips

  • Layer the light. Use the calculator for the general (ambient) layer, then add task lighting at worktops and desks and accent lighting for art and texture.
  • Pale surfaces raise the utilisation factor. A dark ceiling or deep-coloured walls can cut useful light by a third, so lower the UF if your room colour palette is dark.
  • Daylight comes first. Check daytime light levels with the daylight factor calculator and put perimeter fittings on separate, daylight-linked circuits.
  • Measure irregular rooms with the square footage calculator first.
  • Keep downlights about half their spacing from walls, and line them up with furniture, not just the room outline.

Want to see how a room looks with warmer, cooler or evening light before choosing fittings? Upload a photo and try Relight.

From numbers to pictures

See the space before it's built.

Once the plan works on paper, BasedFrame turns a sketch, a massing model or a site photo into a photoreal render in seconds. Try Sketch to Render or Room Redesign with free credits.

Try BasedFrame free

FAQ

Lighting Calculator FAQ

How many lumens do I need for a room?

Multiply the target illuminance in lux by the floor area in square metres, then divide by the utilisation and maintenance factors. A 20 m² living room at 150 lux with factors of 0.6 and 0.8 needs 150 × 20 ÷ 0.48 ≈ 6,250 lumens. In feet, footcandles × ft² gives lumens in the same way.

What is the difference between lux and lumens?

Lumens measure the total light a lamp gives out. Lux measures how much of that light lands on a surface: one lux is one lumen per square metre. A footcandle is one lumen per square foot, which is about 10.76 lux.

How many lux does a kitchen need?

Around 300 lux for general kitchen lighting and 500 lux on worktops where you prepare food. Most designers achieve this with a general layer of downlights plus under-cabinet strips over the counters, rather than flooding the whole room to 500 lux.

How many lux do I need for an office?

European standard EN 12464-1 and IES guidance both point to about 500 lux on the desk for computer and paper work, with 300 lux acceptable for circulation areas within the office. Meeting rooms are usually 300 to 500 lux and corridors 100 lux.

What is the utilisation factor?

The utilisation factor (also called coefficient of utilisation, CU) is the share of lamp lumens that actually reaches the working plane. It depends on the fitting's light distribution, the room proportions and how reflective the ceiling, walls and floor are. 0.5 to 0.7 is typical for a pale room with downlights or panels; dark rooms and deep fittings can drop below 0.4.

What is the maintenance factor?

The maintenance factor allows for light output falling over time as LEDs age and fittings and room surfaces get dirty. A value of 0.8 is a sensible default for clean interiors with LED fittings. Dusty or hard-to-clean spaces may need 0.6 to 0.7.

How many watts of LED do I need per square metre?

Divide the lumens needed by the efficacy of the fittings. Good LED fittings deliver 90 to 130 lumens per watt, so a 300 lux room usually needs around 4 to 8 W/m². Energy codes such as ASHRAE 90.1 and IECC set maximum lighting power densities by space type.

How far apart should recessed lights be?

A common rule is to space downlights at no more than about 1 to 1.5 times the mounting height, and half that distance from walls. In a room with a 2.4 m (8 ft) ceiling, that means roughly 1.2 to 1.8 m (4 to 6 ft) apart. Check the spacing-to-height ratio on the fitting's data sheet.