Room Heat Loss Calculator

Estimate the heat a room loses through its walls, windows, roof and floor, plus air leakage, to size radiators, heat pumps and heaters.

Free · No sign-up · Runs in your browser

How to use the room heat loss calculator

A room heat loss calculation tells you how much heat a room needs on the coldest design day to stay at a comfortable temperature. It is the starting point for sizing radiators, underfloor heating, heat pumps and electric heaters, and for comparing the effect of new windows or insulation. This calculator follows the standard steady-state method used in heat loss surveys: fabric loss through each element plus the loss from air changes.

  1. Choose units. Metric mode uses metres, W/m²K and °C and reports watts. US mode uses feet, BTU/h·ft²·°F and °F and reports BTU per hour. Both show the other unit too.
  2. Enter the room size and the length of wall that faces outside. Only exterior walls lose heat to the outside.
  3. Enter the window and door areas in those walls and the U-value of each element. They are taken out of the gross wall area.
  4. Enter the roof and floor U-values, or zero if there is a heated room above or below.
  5. Set the temperatures and air change rate. Use your local outdoor design temperature rather than a typical day.

Heat loss formulas

Fabric loss = Σ (U × A) × ΔT, where ΔT = inside − outside temperature
Net wall area = exterior wall length × height − windows − doors
Ventilation loss = 0.33 × ACH × V × ΔT (W, metric) · 0.018 × ACH × V × ΔT (BTU/h, ft³ and °F)
Total = fabric + ventilation · 1 W = 3.412 BTU/h

The 0.33 factor is the heat capacity of air, about 0.33 Wh per cubic metre per kelvin; 0.018 is the imperial equivalent in BTU per cubic foot per °F. The roof and floor are taken as the room's floor area. This is a simplified method: it treats the ground like outdoor air and ignores thermal bridges, so use a ground-floor U-value that already accounts for the soil and add a margin for bridging in older buildings.

ElementOlder, uninsulated (W/m²K)Modern, insulated (W/m²K)
Solid or cavity wall1.5–2.10.18–0.30
Window4.8 (single) / 2.8 (old double)0.8–1.4
Roof or loft2.00.11–0.16
Ground floor0.70.13–0.25
External door3.01.0–1.8

To convert, 1 W/m²K = 0.176 BTU/h·ft²·°F. An R-38 ceiling is about U 0.026 in imperial units, and a modern code wall around U 0.06.

Worked examples

A corner living room in metric

A 5 × 4 m room with a 2.5 m ceiling has 9 m of exterior wall, or 22.5 m² gross. Taking out 3 m² of windows leaves 19.5 m² at U 0.30, which is 5.85 W/K. The windows add 3 × 1.4 = 4.2 W/K, the roof 20 × 0.16 = 3.2 and the floor 20 × 0.25 = 5.0, for 18.25 W/K in total. At 21 °C inside and −3 °C outside, ΔT is 24 K, so the fabric loss is 438 W. One air change per hour in the 50 m³ room adds 0.33 × 1 × 50 × 24 = 396 W. The total is 834 W, about 2,850 BTU/h, or 42 W per square metre of floor.

A bedroom in feet

A 16 × 14 ft bedroom with 8 ft ceilings has 30 ft of exterior wall, 240 ft² gross. With 30 ft² of windows at U 0.30, the net wall is 210 ft² at U 0.06, giving 12.6 + 9.0 BTU/h·°F. An R-38 ceiling adds 224 × 0.026 = 5.8, and the floor is over a heated room. At 70 °F inside and 10 °F outside, the fabric loss is 27.4 × 60 = 1,645 BTU/h. Half an air change per hour in the 1,792 ft³ room adds 0.018 × 0.5 × 1,792 × 60 = 968 BTU/h, so the room needs about 2,610 BTU/h, or 766 W.

Who this calculator helps

  • Architects testing how window sizes and insulation levels change the heating load at concept stage.
  • Heating engineers and heat pump installers doing a quick room-by-room check before a full survey.
  • Retrofit designers showing clients the effect of new glazing, loft insulation or draught-proofing.
  • Homeowners sizing a radiator or electric heater for one room.

Practical tips

Planning a retrofit with new windows and finishes? Show the client the result on a photo of their room with Room Redesign.

From numbers to pictures

See the space before it's built.

Once the plan works on paper, BasedFrame turns a sketch, a massing model or a site photo into a photoreal render in seconds. Try Sketch to Render or Room Redesign with free credits.

Try BasedFrame free

FAQ

Room Heat Loss Calculator FAQ

How do I calculate the heat loss of a room?

Add up the fabric loss through each element, U-value × area × temperature difference, and add the ventilation loss, 0.33 × air changes per hour × room volume × temperature difference in watts. For a 5 × 4 × 2.5 m room with a fabric UA of 18.25 W/K, one air change per hour and a 24 °C difference, that is 438 + 396 = 834 W.

What temperature difference should I use?

Use the inside design temperature minus the outdoor design temperature for your location, not an average winter day. Living rooms are commonly designed for 20–21 °C (68–70 °F) and bathrooms for 22 °C. Outdoor design temperatures come from local climate data, such as the 99% winter dry-bulb in ASHRAE tables or national heat pump design guides.

What is a U-value?

A U-value is the rate of heat flow through one square metre (or square foot) of a building element for each degree of temperature difference, in W/m²K or BTU/h·ft²·°F. Lower is better. It is the reciprocal of the total R-value, so you can work it out from a wall build-up with the R-value calculator.

How do I convert watts to BTU per hour?

Multiply watts by 3.412 to get BTU/h, and divide BTU/h by 3.412 to get watts. An 834 W room needs about 2,850 BTU/h of heat. In imperial units the U-value is already in BTU/h·ft²·°F, so U × A × ΔT gives BTU/h directly.

Why is the ventilation heat loss so large?

Cold outside air has to be warmed to room temperature, and air leakage in older homes can be one to two air changes per hour. In a well-insulated room the air change loss is often as big as the fabric loss. Draught-proofing and heat recovery ventilation are the main ways to cut it.

What air change rate should I use?

Typical design values are about 0.5 ACH for a modern, airtight home, 1.0 for an average older home, and 1.5 to 2.0 for draughty rooms or rooms with open fireplaces. Kitchens and bathrooms are often given higher rates. If you have a blower door result, use it.

Should I include floors and ceilings next to heated rooms?

No. Only count elements that separate the room from outside, the ground, an unheated loft or another unheated space. Set the area or U-value to zero for a ceiling below a heated room or a floor above one. For floors on the ground, use a ground-floor U-value, which already accounts for the earth.

How big a radiator or heat pump do I need?

Size each emitter to at least the room heat loss at design conditions, and add up the rooms for the whole-house load. Many designers add a 10–20% margin for intermittent heating. Radiator outputs are quoted at a temperature difference, often ΔT50, so check the output at the lower flow temperatures heat pumps use.